GENERAL ELECTRICAL NOTES NO MORE THAN SIX CURRENT CARRYING CONDUCTORS (INCLUDING NEUTRAL CONDUCTORS) IN ANY ONE CONDUIT CARRYING 20-AMP LIGHTING OR RECEPTACLE LOADS WITHOUT DERATING IN ACCORDANCE WITH NEC ARTICLE 31 0. ALL OTHER CIRCUITS SHALL BE IN A DEDICATED CONDUIT. PROVIDE GROUND CONDUCTOR IN ALL CONDUITS. SIZE PER NATIONAL ELECTRIC CODE. ALL WIRING SHALL COMPLY WITH THE LATEST EDITION OF THE INDIANA ELECTRIC CODE AND COMPLY WITH COUNTY AND/OR LOCAL JURISDICTION HAVING AUTHORITY IN THAT AREA. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR THE EXACT LOCATION AND ROUGH-IN REQUIREMENTS FOR ALL MECHANICAL EQUIPMENT AND PIPING BEFORE ROUGH-IN. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES AND OWNER BEFORE WIRING IS TO BEGIN TO VERIFY ALL OTHER CONDITIONS SO THAT WIRING WILL NOT INTERFERE WITH THE OTHER TRADES. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ENTIRE ELECTRICAL SYSTEM SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. ALL MATERIALS USED IN THE WORK SHALL BE APPROVED BY THE UNDERWRITER'S LABORATORIES, INC.. AND SHALL BEAR THEIR LABEL THE CONTRACTOR SHALL, AT HIS/HER OWN EXPENSE, OBTAIN ALL PERMITS, INSPECTIONS, CERTIFICATES, AND LICENSE REQUIRED BY LAW FOR THE EXECUTION OF WORK TO BE PERFORMED. THE ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED, SHALL FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT AS INDICATED ON THE DRAWINGS. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF FIRST CLASS CONSTRUCTION, AND SHALL BE THE PRODUCT OF AN ESTABLISHED AND REPUTABLE MANUFACTURER, AND SHALL BE DESIGNED TD PERFORM THE SERVICE REQUIRED. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL HARDWARE, LAMPS, ACCESSORIES, ETC. AS REQUIRED FOR A COMPLETE AND WORKING SYSTEM. MULTI-WIRE (SHARED NEUTRAL CIRCUITS) SHALL NOT BE USED. PROVIDE A NEUTRAL CONDUCTOR FOR EACH LINE-TD-NEUTRAL CIRCUIT. ALL POWER AND CONTROL CIRCUIT WIRING USED SHALL BE '1HHN" OR '1HWN" COPPER UNLESS OTHERWISE SPECIFIED OR REQUIRED BY CODE. PER NEC 310.10, ALL WIRING SHALL BE SIZED TO COORDINATE WITH TEMPERATURE RATINGS OF TERMINATIONS. LISTED WIRE SIZES ON PANELBOARD SCHEDULES ARE MINIMUM SIZES. SIZE WIRE TD MEET TEMPERATURE AND VOLTAGE DROP REQUIREMENTS. PROVIDE A PULL ROPE IN ALL SPARE CONDUITS. PROVIDE ID TAG AT EACH END OF PULL ROPE IDENTIFYING LOCATION OF OPPOSITE END. ELECTRICAL SYMBOLS ARE NOT SHOWN TD SCALE. WHEN DEVICES ARE SHOWN ADJACENT, INSTALL IN ADJACENT BOXES. COMPLY WITH BOX FILL REQUIREMENTS OF NEC ARTICLE 314. PROVIDE CONDUIT EXPANSION FITTINGS WHERE CROSSING BUILDING EXPANSION JOINTS. ALL SAFETY SWITCHES SHALL BE "HEAVY DUTY" OWNER RESERVES FIRST RIGHTS TD ANY REMOVED EQUIPMENT AND MATERIALS. ALL UNWANTED EQUIPMENT AND MATERIALS SHALL BE DISCARDED BY CONTRACTOR PER LOCAL, STATE AND FEDERAL REGULATIONS AT NO ADDITIONAL COST TO THE OWNER. WHILE THESE PLANS HAVE IN BEST EFFORT TRIED TD CAPTURE THE POWER AND CONTROL SCOPE FOR THE BASIS OF DESIGN SCREEN, GRIT REMOVAL AND WET WEATHER FILTER SYSTEMS, IT SHALL BE THE BIDDING CONTRACTORS RESPONSIBILITY TO FAMILIARIZE THEMSELVES WITH THE CIVIL PLANS AND PROCESS EQUIPMENT SPECIFICATIONS OR ADDITIONAL INFORMATION PRIOR TO BID. IF SHOP DRAWINGS ARE APPROVED FOR A DIFFERENT MANUFACTURER THAN WHAT IS SHOWN, IT SHALL BE DONE SO AT NO ADDITIONAL COST TO THE OWNER IF INSTALLATION IS MORE OR LESS DIFFERENT THAN WHAT IS DEPICTED ON THESE ELECTRICAL DRAWINGS. ALL QUESTIONS OR CLARIFICATIONS SHALL BE DISCUSSED WITH THE ENGINEER PRIOR TO BID. CONTRACTOR IS TO SEPARATE ALL POWER AND CONTROL CONDUITS, ALSO SEPARATE DIGITAL, ANALOG, ETHERNET, FIBER AND DATA. FIBER IS TO BE INSTALLED IN 2" CONDU I T WITH 90 DEGREE SWEEPING ELBOWS. ALL BURIED CONDUITS SHALL BE SCH, 80 PVC WITH MINIMUM 24' COVER WITH WARNING TAPE INSTALLED IN THc Tl1ENCH 12' CO'/ER, ALL EXPOSED CONDUITS OUTSIDE SHALL BE ALUMINUM ,Ast<N<D WITH 5TAINc,ss HARDAR!t. MINIMUM CONDUIT sllE IS I' EXCEPT FbR SWITCH LEGS WHICH CAN Ile Y.". iYPlcALLY us, bONO $W•�i' ,UllJWS, tONliUITS SHOWN ON SIT� PLAN bR 01':fAILS ARit FOR REFtR,NCE ONLY AND ARit NOT NECESSARlbY iNTENDEfl itl iNlilCA1t tXACT QUANTITY OR LOCATION, MNTRAcTtlR Is fti bUANTlri All REOUiREil PULL ANO JyN(lt1iJN B<iXEii �[R NATIONAL [bECTRil; toilE, IN GROUND lioxrn SHALb BE iiUAzlTE OR ENGINEER Ai'PRilvtb EQUAL WITH Gdb6R !i[lEifilil BY twNrn. EXTERIOR �m(cS SHAbl BE iITAINbtss SitEb FASTEN�O WITH ITTAiNLES� l'IARDWARt GONTRACTOR SHALL REFlbL b1tSEL TANK lJf G�NERAfoR iiNGt STARTUP IS SUCCESSFULLY MMPLCTi;'tl. All REQUIRED BYPASS PUMPING OR TEMMRARY PilWER to MAINTAIN flbANf OPERATIONS Is TH[ RESPONSIBILITY or THE GdNTRAGTliiic COOROINAT[ ALL SGHEOULED OUTAGES WITH OWNER A MINIMUM OF 72 HOURS IN ADVANC[. PLUMBING PLAN NOTES 0) EXISTING NIPSCO MAIN TO REMAIN. 0 UPSIZE EXISTING GAS METER AND SERVICE FOR 1,335,000 BTUH TOTAL CONNECTED LOAD AT 2 PSI DELIVERY. 0 PROPOSED 1.1\" METERED GAS SERVICE (2 PSI) TD MAKE UP AIR UNITS. 8 EXISTING GAS SERVICE TO MAINTENANCE BARN TD REMAIN. 0 1" GAS TO MAKE UP AIR UNIT. REFER TO DRAWING HS.01. 0 1.1\" GAS TO MAKE UP AIR UNIT. REFER TO DRAWING H5.01. 0 TAP EXISTING METERED WATER SERVICE AND INSTALL SHUTOFF VALVE w/ ROADWAY BOX. 0 REFER TO DRAWING H5.01 FOR CONTINUATION OF %" WATER SERVICE. 0 REFER TO DRAWING E12.01 FOR CONTINUATION OF 1.1\" WATER SERVICE. @ REFER TO DRAWING E3.01 FOR CONTINUATION OF 2" WATER SERVICE. @ REFER TO DRAWING E13.01 FOR CONTINUATION OF 1" WATER SERVICE. @ PROPOSED YARD HYDRANT, REFER TO DETAIL 1 ON DRAWING C2.06. 1' O" T CONG SLAB / N 6 - w 0. - 30" 30" #5 BARS X ,. BARS @ 12" O.C.E.W. PLACED 2" BELOW TOP OF SLAB, OVER MIN. 6" COMPACTED SUB-BASE . . . . @ 12" o.c. . 4 · -' 11f 1 fi I _, . • • • . .. "· T I il :, . . . • • ·1�1 • • ' Il l � . • .. . ..... , 11 r, - •• M ' ·' 12" WIDTH OF GENERATOR 12" No. 6 � � CONT., GENERATOR PAD DETAIL NOT TO SCALE I 1 TYP. e- - J , ------- --.., _____ ---:.e-- - - - __,., ---- �- - - " ' II " ' ' II " ,, " ' --e--_ - -o--- - - --0- - (3) 480V-3• POWER- -� (MDPA-4)(MDPA-5)(MDPA-6) 12ov-1• POWER (A-22) / _,..------ �MAKE U�IR-;;;: ,/ H1.02 (MAU-2) / � - - - - --1 / PROPOSED 800A-3P SERVICE ENTRANCE RATED, AUTOMATIC TRANSFER SWITCH I PROPOSED 500KW STANDBY DIESEL GENERATOR THREE FLOATS -PUMP OFF -PUMP ON -HIGH LEVEL ·, ·' .-, ' ., .. - - ,, I " . ��� l l n :, I !I 11 II SLUDGE DRAIN " ,, II ' EXISTING SLUDG DRYING BEDS ' ' ' " - Ii 'I 11 : 1 I I! 11 11 11 II II II II " " " ' " " "" ' ,, II , r �( " " " " " ' " ' """ I ' ' " """ " " " " " II " ' ,, ,," ,, ' " ,, " ' " " ,. 11 II ,, ,, 1: :: ,I ,r- ----- -- - - - ----"' 11 t • II ' ' " . I .. ii , . - - ·- , '- _jl)) JL 11 I 0:-.,.....-- - - - - JI -<=---�..:-- _..,...U.__JL ......u.. jj lJ .JL II 11 ·· -· · =======--====·=·=======�==-i .�;=;;c��=====���"� :S ����:�:������:::::1--= - -_J --- -------0--------- ----&-� - NEW EFFLUENT METERING STRUCTURE AND SAMPLER___ - - A' "\\ I --. � - ·-- HINGED COVER INSTALL CLASS I DIV. 1 1 RATED CONDUIT SEALOFFS FROM DISCONNECT TO JUNCTION BOX JJ. SIZED BY CONTRACTOR JUNCTION BOX WlTBVENTS NEIIA4X S.S. ' I I / I / I I POWER DISTRIBUTION BLOCKS MOUNTED TO BACKPANEL INSIDE JUNCTION BOX INSTALL CABLE GRIPS TO SUPPORT CABLE OUT OF JUNCTION BOX (TYP.) \ I \ \ VENTED ALUMINUM WIRE MESH CABLE GUARD w/ PAD LOCKABLE ACCESS HIGH LEVEL \ :, l · ,,: · · ce ' ' =' · ' t: :- =l . ·',:: .,,=>: : ·"'" ·cc· �.,. · :::· ·,,· ;,' :2:· ;;� · .£" ' : ?. �:'.:: CORE DRILLED ENTRY TO WETWELL (TYP.) ,.. SCUM PUMP JUNCTION BOX DETAIL NOT TO SCALE \ Cl) 0 PROPOSED SITE ELECTRICAL AND PLUMBING PLAN SCALE: 1" = 20' I I • u c:: � z C �EV!SIONS 3/15/24 BID SET C2024 Midwestern Engineers. Inc. 802 West Broadway Street P.O. Bu� 295 Loogootee. Indiana 47553 DATE MARCH 2024 DESIGN A.F.B. DRAWN C.N.M. a.c. CHECK W.A.E. PROJECT NUMBER 2020073-00 E2.02 107 OF 126 I FILE NUMBER _ 43959 Do Not Use Plan Previews for Take Off
Made with FlippingBook
RkJQdWJsaXNoZXIy NjAyODM2