0 © 0 © 0 @ @ @ @ @ @ @ @ @ @ @) PROPOSED 277/480V-30, 4W, FULLY RATED 800A, MAIN LUG ONLY, SQ. D I-LINE POWER DISTRIBUTION PANELBOARD "MDPA" w/ COPPER BUSSING, POWER MEIER PM5563 SMART CELL, 50KA SCCR, INTEGRAL SPO IN NEMA 1 ENCLOSURE. SPO SHALL HAVE SURGE COUNTER, 240KA PER PHASE ANO 120KA PER MOOE. OR ENGINEER APPROVED EQUAL. (4) #6 THWN., (1) #10 CU. GNO., 1" CONDUIT FI L TER EQUIPMENT CONTROL PANEL PROVIDED BY FILTER MANUFACTURER, INSTALLED BY CONTRACTOR. SEE PROCESS EQUIPMENT SPECIFICATIONS FOR ADDITIONAL INFORMATION. FI L TER EQUIPMENT BACKWASH SOLIDS WASTE PUMP VARIABLE FREQUENCY DRIVE TO ABB ULH MODEL ACQ580-31-027A, 4BOV-3¢, 20HP OR ENGINEER APPROVED EQUAL TO STANOAROIZE TO OTHER VFOS INSTALLED THROUGHOUT THE WWTP. HARDWIRED OR ETHERNET INTERNAL TO THE WEI WEATHER FILTER CONTROL PANEL SHALL BE PER MANUFACTURERS RECOMMENDATIONS. (3) #10 THWN, (1) #10 CU. GNO., 1" CONDUIT (3) #12 THWN, (1) #12 CU. GND., 1" CONDUIT (3) #2 THWN, (1) #6 CU. GND., 2" CONDUIT 75KVA TRANSFORMER, 480V-30, 3W Ii PRIMARY, 120/208V-30, 4W WYE SECONDARY, COPPER WINDINGS, NEMA 1 ENCLOSURE ON 4" CONCRETE HOUSEKEEPING PAD (4) #3/0 THWN, (1) #6 CU. GNO., 2" CONDUIT PROPOSED 120/208V-30, 4W, FULLY RATED 200A, MAIN CIRCUIT BREAKER, SQ. 0 NQ POWER DISTRIBUTION PANELBOARD "A" w/ 54 CIRCUIT INTERIOR, COPPER BUSSING, 1 OKA SCCR, INTEGRAL SPD IN NEMA 1 ENCLOSURE. SPD SHALL HAVE SURGE COUNTER, 240KA PER PHASE AND 120KA PER MODE. OR ENGINEER APPROVED EQUAL. (4) #2 THWN, (1) #6 CU. GNO., 2" CONDUIT PROPOSED 120/208V-30, 4W, FULLY RATED 100A, MAIN CIRCUIT BREAKER, SQ. D NQ POWER DISTRIBUTION PANELBOARD "B" w/ 42 CIRCUIT INTERIOR, COPPER BUSSING, 10KA SCCR, INTEGRAL SPO IN NEMA 1 ENCLOSURE. SPO SHALL HAVE SURGE COUNTER, 240KA PER PHASE AND 120KA PER MOOE. OR ENGINEER APPROVED EQUAL. (4) #10 THWN, (1) #10 CU. GNO., 1" CONDUIT 30A-3P NON-FUSIBLE DISCONNECT IN NEMA 4X S.S. ENCLOSURE, MOUNTED TO ALUMINUM UNI-STRUT RACKING AS SHOWN. ABB VFO MODEL ACQ580-31-052A-4, 480V-30, 35HP SUBMERSIBLE PUMP MOTOR, NEMA 1 ENCLOSURE, ETHERNET IN CONDUIT TO SCAOA, EXTERNAL FAULT CONTROL WIRING IN CONDUIT TO DISCONNECT AS INDICATED ON DRAWINGS. OR ENGINEER APPROVED EQUAL. (3) #6 XHHW-2, (1) #10 CU. GNO., 1!," CONDUIT SQ. 0 HEAVY DUTY, 60A-3P NON-FUSIBLE DISCONNECT w/ FIELD INSTALLED AUX. ELECTRICAL INTERLOCK WIRED IN CONDUIT TO VFO EXTERNAL FAULT IN NEMA 4X S.S. ENCLOSURE, MOUNTED TO ALUMINUM UNI-STRUT RACKING AS SHOWN. OR ENGINEER APPROVED EQUAL. CONTINUOUS HINGED NEMA 4X S.S. VENTED JUNCTION BOX 18" ABOVE GRADE. SUPPORT CONDUITS HORIZONTALLY THEN USE CLASS I DIV. I SEAL OFFS PER NEC, TYPICALLY USE MYERS HUBS. ALUMINUM CONDUIT FOR EXPOSED, THEN CONVERT TO SCH. 80 PVC ONCE BURIED. SEPARATE POWER, DIGITAL AND ANALOG. INSTRUMENTATION FOR INFLUENT PUMP STATION WILL BE GROUPED w/ PROCESS PUMP #2 JUNCTION BOX. (3) #12 XHHW-2, (1) #12 CU. GND., 1" CONDUIT ABB VFO MODEL ACQ580-31-012A-4, 480V-30, 5.8HP SUBMERSIBLE PUMP MOTOR, NEMA 1 ENCLOSURE, ETHERNET IN CONDUIT TO SCADA, EXTERNAL FAULT CONTROL WIRING IN CONDUIT TO DISCONNECT AS INDICATED ON DRAWINGS. OR ENGINEER APPROVED EQUAL. @ @ @ @ @ @ ® @ ® @ @) @ @ @ ® @ @) @ @ @ PROPOSED UNDERGROUND PRIMARY ilY NIPSCO • -· PROPOSED 217/480V�J¢, 4W ELECTRIC SERVICE, CTS, METtRING, PAD MOUNT TRANSFORMER AND • -· -@] TERMINATIONS BY UTlblfi, CQNCRCTE PAD AND SECONDARY INSTALLED BY CdNTRACTOR 2 RUNS -=- -2 RlJNS (4) #600 MCM THWN 4" CONDUIT ' (4) #300 MCM THWN, (1) #1/0 CU. GND, 4" CONDUIT KEY NOTES SQ. 0 HEAVY DUTY, 30A-3P NON-FUSIBLE DISCONNECT w/ FIELD INSTALLED AUX. ELECTRICAL INTERLOCK WIRED IN CONDUIT TO VFO EXTERNAL FAULT IN NEMA 4X S.S. ENCLOSURE, MOUNTED TO ALUMINUM UNI-STRUT RACKING AS SHOWN. OR ENGINEER APPROVED EQUAL. GRIT REMOVAL EQUIPMENT CONTROL PANEL PROVIDED BY GRIT REMOVAL EQUIPMENT MANUFACTURER, INSTALLED BY CONTRACTOR. SEE PROCESS EQUIPMENT SPECIFICATIONS FOR ADDITIONAL INFORMATION. (3) #12 THWN, (1) #12 CU. GNO., 1" CONDUIT INSTALLED CLASS I DIV. II PER NEC LOCAL DISCONNECT PER MANUFACTURER'S INSTALLATION RECOMMENDATIONS, 30A-3P SUITABLE FOR CLASS I DIV. II HAZARDOUS LOCATION PER NEC. HEADWORKS SCREEN/SCAOA CONTROL PANEL w/ INTEGRAL VFO, PLC AND TOUCHSCREEN IN NEMA 1 ENCLOSURE. SEE PROCESS EQUIPMENT AND ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION. RAS/WAS, CLARIFIERS AND EFFLUENT PUMP STATION SCADA CONTROL PANEL w/ INTEGRAL VFOS, MOTOR STARTERS, PLC AND TOUCHSCREEN IN NEMA 4X S.S. ENCLOSURE. FIELD VERIFY EXACT LOCATION w/ OWNER AND ENGINEER DURING CONSTRUCTION PRIOR TO INSTALLATION. SEE ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION. ABB VFO MODEL ACQ580-31-012A, 480V-30, 5.8HP SUBMERSIBLE PUMP MOTOR, NEMA 1 ENCLOSURE, HARDWIRED CONTROL TO SCADA PER 1/0 LIST. ABB VFO MODEL ACQ580-31-012A, 480V-30, 7.5HP SUBMERSIBLE PUMP MOTOR, NEMA 1 ENCLOSURE, HARDWIRED CONTROL TO SCADA PER 1/0 LIST. PUMP CABLING FOR POWER, SEAL LEAK AND OVERTEMP PROVIDED BY PUMP MANUFACTURER, INSTALLED BY CONTRACTOR (NO SPLICES). CONTRACTOR TO PROVIDE AND INSTALL NEW 60A-2P CIRCUIT BREAKER IN EXISTING SQ. D HOMELINE LOAD CENTER TO FEED NEW CHEMICAL FEED BUILDING PANEL. CONTRACTOR TO PROVIDE AND INSTALL NEW SQ. D HOMELINE 12 CKT. LOAO CENTER w/ 60A MCB IN NEMA 1 ENCLOSURE. OR ENGINEER APPROVED EQUAL. (3) #2/0 THWN, (1) #6 CU. GND., 2" CONDUIT BACKWASH HOLDING TANK (BWH) SCADA CONTROL PANEL w/ INTEGRAL MOTOR STARTERS, EXTERNALLY MOUNTED 5KVA 10TRANSFORMER, PLC AND TOUCHSCREEN IN NEMA 4X S.S. ENCLOSURE. FIELD VERIFY EXACT LOCATION w/ OWNER AND ENGINEER DURING CONSTRUCTION PRIOR TO INSTALLATION. SEE ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION. (3) #8 THWN, (1) #8 CU. GND., 1" CONDUIT (2) #12 THWN, (1) #12 CU. GND., (3) #8 THWN, (1) #10 CU. GND., 1" CONDUIT CONTRACTOR TO PROVIDE ANO INSTALL NEW SQ. D HOMELINE 12 CKT. LOAD CENTER w/ 40A MCB IN NEMA 1 ENCLOSURE. (2) #12 THWN, (1) #12 CU. GND., 1" CONDUIT CONTRACTOR TO PROVIDE AND INSTALL SWITCHED OUTLET FOR CORD ANO PLUG CONNECTED POLYMER FEED PUMP. OWNER TO MANUALLY OPERATE PUMP DURING DEWATERING OPERATION. MANUAL SWITCH FOR EXHAUST FAN OPERATION, INTERLOCK FAN w/ MOTORIZED LOUVER/DAMPER. BLOWER ENCLOSURES ARE EQUIPPED w/ 120V VENTILATION FANS THAT ARE TO BE INTERLOCKED TO OPERATE WHEN BLOWERS ARE RUNNING VIA INTERNAL RELAY. CONTRACTOR TO RUN I)." CONTROL CONDUIT AND WIRING FROM EXISTING BLOWER CONTROL PANEL TO CHEMICAL FEED BUILDING SCADA RTU PER 1/0 LIST TO MONITOR BLOWER AND WASTE SLUDGE PUMP RUN STATUS. PROPOSED 800A-3P ASCO, )-8ooA-3P PROPOSED 500KW STANDBY DIESEL 800A-3P SERVICE ENTRANCE RATED, GENERATOR IN STANDARD WEATHERPROOF DELAYED TRANSITION, 100% RATED l ,, ., _ A -@ ENCLOSURE PROVIDED ANO INSTALLED BY MAIN, AUTOMATIC TRANSFER SWITCH .. . CONTRACTOR, SEE SPECIFICATIONS FOR IN NEMA 1 ENCLOSURE PROVIDED ADDITIONAL INFORMATION. ANO INSTALLED BY CONTRACTOR. r �� , 3 RUNS #3/0 BARE CU. GND. IN CONDUIT J (4) #300 MCM THWN (1) #1/0 CU. GND. 3" CONDUIT EXOTHERMICALLY WELDED TO (3) 8 Jf¢x10' CU. CLAD GND. RODS ON 1O' TRIANGULAR SPACING 1 2 3 4 5 6 7 8 9 10 11 12 L L ! ! ! ! ! L L L L L_ }-6DA-3P }-60A-3P I si D I L_ }-125A-3P }-4DOA-3P )-2DA-3P )-20A-3P )-20A-3P )-soA-3P )-8oA-3P )-8oA-3P )-20A-3P )-20A-3P )-15A-3P §] , , v v v , , ... ... " 0 0 : @' @: 0 0 0 0 0' 0' 0: 0 . ' , ' , ' . ' . ' ' PROPOSED WET WEATHER FILTER EQUIPMENT CONTROL PANEL 0 • • / / / 60A-3P ·- • @ @ @ @ @ @ @) @) )-15A-3P 3 2 1 A :, 75 KVA @) ..1.. I I I • , v v , , ... " -r- NEMA 0 @' @: 0� @ @ @ @: @: SIZE 0 )-20A-2P )-20A-3P )-5oA-3P ' ' : . � . � .t ' @ I @ I @ I @ / @ / 200A -- VFO 0 0 @ NEMA � MCB SIZE DO , , , v " " @ @ @ @' @' 0: , , PANEL "A" 0 0 : . ' WEI WEATHER ' ., FILTER BUILDING @1 JUNCTION BOX @1 JUNCTION BOX @ JS @ JS TANK MOUNTE: Js -.., UV POC #1 UV POC #2 UV HSC @' JUNCTION BOX 20HP , 277/480V-3•. 277/48DV-30, 480V-3¢, 3W @ @ @ @ @ @ . : 4W 8 FLA 4W 8 FLA 3 FLA -.., -.., r /' r' BACKWASH 100A 35HP 35HP 35HP 5.BHP 5.BHP 2.7HP SOLIDS MCB ,._ ,._ 2HP / / WASTE PUMP 42 CKT. ' 480V-3¢ WET WEI WEI PROCESS PROCESS SCUM CONTROL DRIVE 27 FLA PANEL "B'' 2 RUNS WEATHER WEATHER WEATHER PUMP #1 PUMP #2 PUMP TRANSFORMER MOTOR HEADWORKS (4) #3/0 THWN PUMP #1 PUMP #2 PUMP #3 480V-3¢ 480V-3• 480V-3¢ 48DV-30 BUILDING (1) #2 CU. GNO. 480V-3¢ 480V-3\ll 480V-3\ll 6.2 FLA 6.2 FLA 3.7 FLA 3.4 FLA 3" CONDUIT 42 FLA 42 FLA 42 FLA MATCH LINE - SEE SHT. E103 FOR CONTINUATION PROPOSED POWER DISTRIBUTION ONE LINE DIAGRAM NOT TO SCALE 13 L @) @ ® @ @ @ FLOAT CONTROLLED SCUM PUMP CONTROL PANEL TO INCLUDE CIRCUIT BREAKER DISCONNECT, NEMA RATED MOTOR STARTER, SELECTOR SWITCHES, ELAPSED TIME MEIER, PILOT LIGHTS AND ALARM HORN INSIDE NEMA 4X S.S. ENCLOSURE w/ INNER SWING OUT DOOR. JUNCTION BOX ABOVE WEIWELL TO BE INCLUDED IN SCOPE AS SHOWN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. (3) #10 XHHW-2, (1) #10 CU. GNO., 1" CONDUIT EXISTING PUMPS AND CABLES TO BE REUSED. ABB VFO MODEL ACQ58D-31-027A-4, 480V-3•. 20 HP BLOWER MOTOR, NEMA 1 ENCLOSURE, ETHERNET IN CONDUIT TO SCADA. OR ENGINEER APPROVED EQUAL. THE CONTRACTOR SHALL PROVIDE AND PERMANENTLY INSTALL A WEATHERPROOF, FEMALE, 48DV-3¢, 3 POLE, 20A, LOCKING RECEPTACLE AT THE PUMP LOCATIONS DESIGNATED (MIN. 18" ABOVE TANK). FIELD VERIFY EXACT LOCATION w/ OWNER DURING CONSTRUCTION PRIOR TO INSTALLATION. HAROWIRE MALE PLUG ON SUBMERSIBLE PUMP CABLE TO MATCH RECEPTACLE. PROVIDE NEMA SIZE O COMBINATION MOTOR STARTER/NON-FUSIBLE DISCONNECT IN NEMA 4X S.S. ENCLOSURE, SQ. D 8538 SSW 11 FOR DIGESTER DECANT PUMP. PROVIDE FUSED CONTROL TRANSFORMER, PUSH TO TEST RUN-FAIL PILOT LIGHTS, H-0-A SWITCH, PHASE FAILURE/REVERSAL RELAY AND AUX CONTACTS FOR MONITORING RUN STATUS (ON/OFF) AND ALARM BACK TO SCAOA FOR MONITORING (FUTURE). 14 L Ll:GEND ,-·----- NEW CONDUIT, WIRINIJ, AND EQUll'MtNt __ EXISfiNG CONDUIT, WIRING, ANO EQUIPMENT }-3DA-3P }-3DA-3P 0 PROPOSED GRIT REMOVAL CONTROL PANEL _ .. , ---. 1 2 3 }-3DA-3P I I I �@ }-2DA-3P }-2DA-3P }-2DA-3P ..1.. ..1.. ..1.. -- -- -- , @ 0 NEMA NEMA NEMA SIZE DO SIZE 00 SIZE 1 , , @ ." r-.., @ @ 3HP @ / @ / @ / SCREEN DRIVE 480V-3¢ , , " 4.8 FLA @ @ @) , -.., IHP IHP 7.5HP '- J ' ' GRIT PADDLE GRIT GRIT PUMP DRIVE CLASSIFIER 480V-3¢ 480V-3¢ 480V-3• 11 FLA 1.7 FLA 1.7 FLA REVISIONS 3/15/24 BID SET C2024 Midweslcm Engineers. Inc, 802 Wcs1Broadway Street P.O. Bo.� 295 Loogootee, Indiana 47553 DATE MARCH 2024 DES!GN A.F.B. DRAWN C.N.M. Q.C. CHECK W.A.E. PROJECT NUMBER 2020073-00 E102 124 OF 126 I FILE NUMBER I 43942 Do Not Use Plan Previews for Take Off

RkJQdWJsaXNoZXIy NjAyODM2