400A AUTOMATIC TRANSFER SWITCH SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 INCOMING LJNE MAIN LUGS ONLY D D El El2 3 4 5 EXISTING MCC ELEVATION NOT TO SCALE; TO BE REMOVED �- - EXISTING 277/480V-30, 4W TRANSFORMER UTILITY/ •c BY DUKE ENERGY TO BE REMOVED BY L • DUKE ENERGY AT COMPLETION OF PROJECT I l �-,"- 0 - -0VERHEAD SECONDARY TO BE CONTRACTOR - � REMOVED BY DUKE ENERGY -1 -- EXISTING 480V-3¢r-------1 400A-3P ASCO AUTOMATIC TRANSFER SWITCH, MODEL C940340099XC >'-- --IM ' - EXISTING METER, CT & MITER BASE TO BE 1 � __,, REMOVED BY DUKE ENERGY AT COMPLETION � - -- " OF PROJECT. ALL OTHER EQUIPMENT ::k REMOVED BY CONTRACTOR. • \ c--,,L--- -EXISTING 400A-3P SERVICE ENTRANCE RATED DISCONNECT 400A-3R • 1-,///, ,�--EXISTING STANDBY GENERATOR, 230 KW, 277/480V-3¢, 4W \ L,/,, {Gy ECTION REMOVE HOUSEKEEP I NG PAD FLUSH, LEVEL TO EXISTING PAN E L 225.AMPERES PP1 3J,Jl VOLTS _ _ � -_::==:' WIRE CI R CUIT NO ITEM FEED 1 30 KVA TRANSFORMER 3 AERATOR MOTOR #1 15 AERATOR M O T O R #3 4PUMP #2 LIFT STATION PUMP #2 TO BE REMOVED SECTION _MLQ MAIN CONNECTION _ _J PHAS E �.KAIC --c � W I RE CU. _____.c.,,, [SJJ�G._W'I/I P LOCATION _ SURfhCEMOUNTING __ .... S.E.l. SIZE � PS POL E 3 BUS POL E W I RE AMPS SIZE IT E M F EE D CONTROL PANEL CIRCUIT NO. +- 12 20 1 2 20 1 2 20 10 3 3 8 40 -+ 3 A� B C A B C A 8 3 3 L 20 12 2 0 20 -I 2 ' r 4 I 6 30 40 10 f LIFT STATION PUMP - #1 8 1LIFT STATION PUMP #3 L 8 I +,, SE ON 3 NOTE: CONTRACTOR TO REMOVE ALL ELECTRICAL EQUIPMENT AND APPURTENANCES IN THEIR ENTIRETY IF ABANDONED OR REPLACED AS A PART OF THIS PROJECT_ THIS SHALL INCLUDE, BUT NOT NECESSARILY BE LIMITED TO MOTOR CONTROL CENTERS, DISCONNECTS, MOTOR STARTERS, TRANSFER SWITCHES, CIRCUIT BREAKERS, SW I TCHES, PLUGS, RACKING, CONCRETE, GENERATOR, POWER/CONTROL WIRE, POWER/CONTROL CONDUIT, MITERING, SENSOR, CONTROL DEVICES, LIGHTS, PUMPS, CONTROL PANELS, ENCLOSURES, TRANSFORMERS, ITC. PANEL ---� 1QQ AMPER E S __ _ J_2Q,/2_Qll_ VOLTS 4 W I RE __JM, CRMAIN CONNECTION __ _ ,3. PHAS E -------- -� F XlSIJNG____W_WIE_ LOCATION LP1 _.,_KAIC -5.UfilACE_ MOUNTING �S. E .L. CI R CUIT NO ITEM FEED I W I R E . I cu I SIZ E AMPS I POL E i suS W I RE POL E AMPS SIZ E ITEM F EE D CI R CUIT NO_ 3 � 7 9 11 JPPER LEVE _ L _ B _ U _I L _OI_ N _ G _ L_ IG _ H _ TI _ N _ G _+--�r� 2 ----+ �2�� A -_+--�' ----+ � 2 0�+---� '2��P� O � L � E �# � 1________ I ', EXTERIOR BUILDING LIGHTING 12 20 , 1 8 _( 1 . 1 , 20 12 MIDDLE LEVEL BUILDING J4 BUILDING RECEPTAC L ES & EF-4 12 20 --,----- 1 ·- C 1 1 2 0 1 2 MIDDLE LEVEL & LOWER RECEPTACU�-�- RE - CE- P-TAC - LE DIG A LARM CABINET 1 2 20 I 1 A 1 I 20 12 L OWER LEVEL LIGHT j__ 8 INCUBATOR 12 20 1 B 1 1 20 12 LAB COUNTER RECEPTACLE __J_ 10 UNDER C O UNTER REFRIGER A TOR 1 2 2 0 I 1 C :--t-?0 12 LAB COUNTER RECEPT A CLE • I 12 � EF 1 & 2 12 20 I 1 A 1 20 12 SPARE _ +.14 15 CL2 ROOM RECEPTACLE 1 2 2 0 1 1 _ 8�__ 1_! - " 2 � 0�� 12 �-t= MM � P �=��=� 16 �7 EF-3 & LAB CENTER RECEPTAC L E I 12 2 0_ 1_ C 1 20 12 FLOW RECORDER FIT-Q7 -- _ 18 19 EF- 5 & t:NC ��+- �12� T; �2� 0 ,__, �1-+ I -A� 1 1 20 12 C L2 LEAK DETECTOR 2 0 21 BUBBLER AIR C O MPRESS O R & CAB. 1 2 2 0 �B 1 2 0 12 !FLOW TRANSMITTER FIT-17 _ _2 2 23 ��SEMENT_EXHAUST � FA �N�-- ��12�1- - , 2� 0 0_ C -- , - 1 _ �2i )______J_2 1WATER HEATER_ _ 24 2 5 SITE RECEPT A CLE ' 12 2 0 1 ' A 2 ' 50 8 THRU WAL L A /C 26 27 SUMP PUMP 1• . 1 , 2 2 r- 2 0 1 T B I - - - - -� 28 � £. OLE LIGHT #2 __ --,--- -�~I _ 2 __0 � 1 c �-' --_ 2 0 12 P O LE LIGHT J4 _30 31 POLE LIG! i!._& RECEPTACLE "# _5_ - -+�1� 2-- 2 �0��'�+ - -A �'��20��12 POL�UGHT � 3 2 33 BLANK 12 2 0 _ 1 B 1 2 0 1 CL2 ROOM LIGHT 34 �E 4 � � r � � � r � r - � - � - z - , - . --- TO - .- & -- --�,�:-:-� ���! , ; i i�� -- � -- -- - 4 E 41 C 1 20 1 2 BLANK 42 TO BE REMOVED, RECONNECT EXISTING LOADS STILL REMAINING AT COMPLETION OF PROJECT TO PROPOSED LIGHTING PANEL "C". NEW CONDUIT A NO WIRE TO BE PROVIDED ANO INSTALLED AS REQUIRED FOR FULLY FUNCTIONAL SYSTEM. SE ION 4 KEY NOTES (D 60A-3P NON-FUSED DISCONNECT IN NEMA 12 ENCLOSURE. (?) 30A-3P NON-FUSED DISCONNECT IN NEMA 12 ENCLOSURE. G) 30A-3P NON-FUSED DISCONNECT IN NEMA 4X s.s ENCLOSURE. SECTI 5 SECT I ON �--- -.--- �- EXIST! 277/48 -30, 4W 600A SQ MOTOR ONTROL NTER CA", COP R BUSSI MAIN G ONLY, TEGRAL S 240K H, IN N Al ENC URE, P 563 POW MITER --- ' ,- - - - --- -, - - -- ·- - L 1 • 3 4A . . - • • ' INCOMI LI AIN '\_g -3P / } 0A-3P LUGS _\ ONLY i VM I PM - J_ - TRA ER PUM '� I 20HP\ ;- I l • rsPDI I :1:y STATION A -- ' 480 -3¢ 27 FLA TRANSFER PUMP #1 48 -3¢ 27 FLA TRANSFER PUMP #2 (DISCO CTURN PUMP / STATI r - - • , 40A-3P IT I f (A ANDONED) lSTATION TO REMAIN AND BE REPURPOSED WITH NEW -, I I ECTED) I - _J CIRCULATI • • \ 40A- P I :1: y PUMP ATION{ --- I -- - c'.J • \ • _, :'!:: I / 15A-3P y ,'� /10HB >-< OV---30 14 FLA RECIRCULATION PUMP #1 T c 1 { / OHP\ 'l- 480v 0 14 FLA RECIRCULATION PUMP #2 / DIGESTER CONTROL PANEL TO BE REPLACEDj WITH NEW ' . • A-3P • "J 50A-3Fl NE � E ( 7 • 7 ) 50A- P • , MA ;'., SIZE 2 � ), I 8 9 • • • "\ 3 -3R J \ 30A-3P • NEMA r:'. SIZE � " NEM L 2 SI • -30A/ A IZE 1 11 f •- • \ 3A / NEMA � SIZE L � " / p ' • I \ A-3P • NEMA SIZ 1 13 • - • ; 3A-3P • • N A ZE 1 - -' 14 , - I -I I __l_ I � EMA I ' - SIZE 1 ( :'!:: " / ,- • \ • NEMA r' SIZ -(--- �I 'l I I G)' • I . /, I ,/ '1 ,/ 3 • I , I @I • I f � 3 3 • I I ' I • I Gl - . / f � Gl I ,--,� 25HP\ ;-</ 48DV-3 4sov/2 34 FLA 34 FLA SLUDGE PRIMARY TRANSFER SLUDGE PUMP PUMP 480V-3¢ 14 FLA RAW SEWAGE PUMP #1 _y 480V-30 14 FLA RAW SEWAGE PUMP #2 480V-30 14 FLA RAW SEWAGE PUMP #3 0-� ); ,.-l_ I 1HP\ 1 --- / 48 -3¢ 2.1 FLA PRIMARY COLLECTOR �UOGE PUMPS TO BE REPLACED WITH NEW #1 ��W PUMPS TO REMAIN, REWIRE PER PROPOSED ONE LINE DIAGRAM ,� I 1HR < SOV---30 2.1 FLA PRIMARY COLLECTOR #2 " y ( p\ � ,,v ,,- � I 1HP \ 2-< --</ 480V-3 480V-3¢ 480V-3¢ 2.1 FLA 2,1 FLA 2,1 FLA PRIMARY SECONDARY SECONDARY COLLECTOR COLLECTOR COLLECTOR #3 #1 \ / #2 DISCONNECTS AND DRIVY MOTORS TO REMAIN, REWIRE PER PROPOSED ONE LINE DIAGRAM ,,v , I� Ii; � J - -'::, 480V-3 1-1 FLA COMM I NUTOR #1 NOTE: INFORMATION ON THIS SHEET IS FOR REFERENCE ONLY. IT SHALL BY THE CONTRACTORS RESPONSIBIL I TY TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID_ EXISTING POWER DISTRIBUTION ONE LINE DIAGRAM NOT TO SCALE � _y ' / /2H� l= 480V 0 1-1 FLA COMMINUTOR #2 I 18 • \_3 3P _i OFF) � NEMA j _SIZE :-,__ " . / ,� I 1HP \ 'l- '\ A-3P (OFF) ;r NEM 'j SI .L_ --,- �- I { ,,-� I 1H -< 20 -• • • I ,/ ( HP 1 ?sov-� 4 V-3> 2.1 FLA WATER SEAL PUMP #1 480V - 3¢ 2.1 FLA WATER SEAL PUMP #2 2.1 FLA WATER SEAL PUMP #3 SEE CONTINUATION ABOVE / EXISTI • 480V-3 • 21 . -• 22 . -, 3 2 •- ,-- - SPARE I S REiSPA SPARE LP1, 10 , 120/20 -30, I � W �CKT _j_ - - --- --- - 3W, 225 SQ, D INE PANE OARD, C PER BUS 3 4 --•-----• - • • 1 20A-3 1 20A-3 1 20A-3 1 20A­ • 0� ' 0� ' 0ffi • 0N � �� /, ✓-�5HP 1 1 -y 480V-30 7.6 FLA MUFFIN MONSTER 25 26 • • • -• ; 225A-3P, • I�pl� . " 0 KVA - :-,'/-\ / SE - 2 ~ NTINUATIO ✓ ELOW / / G, MAIN UG ONLY N NEMA1 NCLOSU 8 ,- • : 30A- • (OF 9 • 10 • 40A­ (O ) / • 1--( REVISIONS BID SET· © 2021 !\lidw�stetTI Engineers. Inc. �02 We.>t Brn�duny Stred ['.0. 13ox 295 Loogoot�. lndi"'l" 47553 DATE SEPT_ 2021 DESIGN A.F.B_ DRAWN C,N_M_ Q.C. CHECK R,D,W_ PROJECT NUMBER 2015078-01 E1 03 1 01 Of 11 4 FlLE NUMBER 41971 Do Not Use Plan Previews for Take Off

RkJQdWJsaXNoZXIy NjAyODM2