PIPING PAINT IDENTIFICATION COLORS SANITARY-DARK GREY RAW WATER-OLIVE GREEN FINISH/POTABLE WATER-DARK BLUE CHLORINE {GAS & SOLUTION) - YELLOW FLUORIDE- LIGHT BLUE PRIMARY COAGULANT- ORANGE CARBON - BLACK POTASSIMUM PERMANGANATE - PURPLE PIPE LABELS SHALL BE INSTALLED EVERY 25' TO 50' ALONG STRAIGHT RUNS. AT ALL CHANGES IN DIRECTION ON BOTH SIDES OF THE TURN, AT BOTH SIDES OF ENTRY POINTS THROUGH THE FLOORS AND WALLS, NEXT TO ALL FLANGES AND VALVES AND SHALL INCLUDE FLOW DIRECTION OF CONTENTS. IDENTIFICATION LABELS/ TAGS SHALL BE INSTALLED ON ALL TANKS, PUMPS, VALVES, METERS AND EQUIPMENT. CHEMICAL FEED PIPING LEGEND CHLORINE GAS SUPER CHLORINATED WATER L ---w--- SUPER CHLORINATED WATER IN EX. CONDUIT POTABLE WATER ---wr--- EX. POTABLE WATER PIPING TO BE REUSED SODIUM FLUORIDE SODIUM FLUORIDE IN EX. CONDUIT -NaMNo4- SODIUM PERMANGANATE ........iW...- SODIUM PERMANGANATE IN EX. CONDUIT ---PH--- PHOSPHATE --- PH--- PHOSPHATE IN EX. CONDUIT VENT PIPE ---v--- PIPE LABEL REQUIREMENTS PIPE MIN LABEL MIN. LETTER DIAMETER SIZE HEIGHT 0.75" TO 1.25" 1" X 8" 0.5" 1.25" TO 2.5" 1" X 8" 0.75" 2.5" TO 8" 2" X 12" 1.25'" 8" TO 10" 3" X 24" 2.5" 10" > 4" X 32" 35" 'v' LJ - Ill • EX. FINISHED FLOOR AUDIBLE ALARM HORN WITH PUSH TO SILENCE BUTION & RED LIGHT OUTSIDE CHLORINE ROOM 1 ,1// w (6) #14 THWN ---' IN CONDUIT w CHLORINE GAS DETECTION SYSTEM CONTROLLER 120 V i w E-"""" NEW BATIERY BACK UP GAS DETECTION SYSTEM RECEIVER MODULE/ ALARM GAS DETECTION SYSTEM SENSOR/ TRANSMITTER L IN CHLORINE ROOM E---E--,--E E E � 2 WIRE CABLE IN PVC CONDUIT �- , w ' ----w--•--w---- W ' ---+-w----w----w · ----w--1--w , ----w' ----w REDUCED PRESSURE BACKFLOW PREVENTER /-jJJ--- is° - - +r-- 1 I I I I I I I I I I I I I I I I I I I I I ' ' w r-+--w----w · -�•---w----w, +---� ,: O ! 1 � N 1 L 2 Mn04 -----NaMn04 __..,.,__NaMn04 ---- CL4---� 2" PVC VENT TO EXTERIOR TERMINATE 1' -0" ABOVE ROOF w/ SCREEN M 0 I I AERALATER No. 1 PROPOSED INJECTION POINTS " - --llr­(_- " 6" INFLUENT FROM WELLS 1, 2&3 I - y %" H.B. -:;:- m mom- I - - I M 'a" "' m m m 1" m 1111(2)1111-� - PROPOSED :z: 1 , · INJECTION POINTS_, � I ! I < I � NaMn04 -----NaMnn(0:_'. 4:_::=� �;'. NaMn04 ------� L--..fww-====1iv=====vwv=====vwi=====-ww- =.:==-;wN :..:.:.:.:.:.:...=vwv -=-=-=-=-=-:..,::;-1 L.-CL2---- CL2 - C L 2 - CL2 �2 L . 2 --..... 1---- CL2 --.1-CL2 CL2 CL2 ll ,----CL2 CL2 CL2 ---- CL2 ----CL2 ---- CL2 CL2 CL2 CL2 m W CL2 W � L2 CL •+---PH·---- -CL2 ---1-CL2 -CL2 , • PH----PH-�---PH----PH----PH--- -- � j FLOW lOPORTIONAL I I 1 ��- L - --.1,-""'\lr"\ I " - - - - llltllll-111 - - - 11 I - Ill ,,_" H.S. PUMPS - - Ill Ill/ - - - - llllblll - - 11 i!: � r JI, ' ; o :-�� LL :;: T I 6 CL 9 2 (j 2. WfP2- PRE I �§ CJ 1 tt:l: I I J 3 WTP1- POST t NI 4. WTP1- PRE ,: dl 11 I _L IX - L J._ I AUTOMATIC � SWITCHOVER VALVE d 0 1,(s: ' "� N .. == "' 0 \ DUAL ELECTRONIC CYLINDER ::§: 0 CHLORINE INJECTORS 1. WTP2- POST 2. WTP2- PRE 3. WTP1- POST 4. WTP1- PRE M 6" EFFLUENT (SOUTH) I � I � \ SCALE L NDICATOR w--•-w' --!,l<!- "'- +4--l C PH PH PH L- - ( ) - -J Q u V � V V I 0 I AERALATER No 2 2" PVC VENT t- V V V TO EXTERIOR t= V V V V V V -v V V V V V V V N -' ,: 0 z N ru "' I a V 0 a. ,. • � "- REGULATORS W---W'--�f--"''--i>+-l CHLORINE TANKS CONTROL TO I 150 LBS EACH) SCADA (TYP } w w,------w , ---�-��M ' �-� DUAL CHLORINE 1 .:i_ :'� Jj w w w w w w w w w w w w w, N -' CYLINDER SCALES -PH - PH- - - - - eH - - PH I a. w�,+,c z a. 0 I " I - 1"H v PH H W ,: ; ,: -CL2- .1 c, s 1)\'/i 1" ' s I w PH - -CL:- . Cl..i 0 w w w L/ w PH PH -PH--PH PHI > -- -��i ,: - 'O :,; -�a t > s I JI,'� " - l '' > s - --- > ,: sl 0 Q_ I,: o,C Lw Ji l z ( N.C. N.C. ��- 8" 1 1 LUENT FROM WELLS 4 & 5 INJECTION PROPOSED t POINTS r Gl.2 5:T '1 i3 - � - - ----- .. 'S ""\f' ---- , , , I - ' � I REDUCED PRESSURE < _J \ BACKFLOW d (,cl CL2 I PREVENTER CL2 � l\.. Ya' I , �M t::::( � -,=..m-6c-f[Nn- Q I"�-<11-- -ll - - 8 ,;-ilr-, "'7-lll-'-111--"r --11----If- - -� + I I 1 8 ' I N -' I r0 ,J r > ' I " r LEVEL ;,= ;,= SENSOR ;,= 0 0 ·""J"' I@] � N C � N.C. .t SOLUTION TANK N.C. 40 GALLON (20'"0 x 38" TALL) - f ' LOW PROFILE SPILL CONTAINMENT SYSTEM, � USA BLUEBOOK STOCK #88792, OR EQUAL non I PROPOSED H.S. PUMPS f� SODIUM FLUORIDE INJECTION POINTS _, � LtJ_:::cL2 CL2 c= Cl2 CL2- CL2 " 1 2 EFFLUENT (EAST) CL2 CC2. CL2 CL2 UPFLOW SATURATOR (NEW AS OF SEPT. 2023) (TOBE REUSED) C ' ' C " - w- � � ' w w l\'7 w w w ( ,., I d L LORINE TANKS '"� I NEW PHOSPHATE FEED IN > EXISTING FLUORIDE CONDUIT ,: z �GU L PH ;:- PH ru PH I I � > > a 4 I a. ,l, :c l_PH --- ,_ > PH PH- r LEVEL SENSOR r SINGLE WALL 140 GALLON ;,= (29"0 x 58" TALL) N.C. 5 GALLON n� DAY TANK 1-w \ w/ � CALE CONC. PEDESTAL LNEW CONCRETE PHOSPHATE CONTAINMENT WALL CL2- CL2 CL2 CL2 Cl2 CL2 N.C. ' � ;,= ;,= ;,= � o 0 N.C. = = V .. CL .2. -- .. GL2 "' CL2 0� < l <I z ru I %'� "' a 1� ¥,tL: N.C. ,: ..l H.B. T 4 NaMn04 < NaMn04' - LEVEL SENSOR N.C. [[] SINGLE WALL 140 GALLON � ;,= (29"0 x 58" TALL) � .,o N.C. N.C. 5 GALLON 1 n� DAY TANK i.... \w! "f CALE I N.C. - V CONG. PEDESTAL L SODIUM PERMANGANATE NEW CONCRETE CONTAINMENT WALL CL2 CL2- CC2 CL2 CC2 CL2 N.C. • ;,= fi I CC2 CL2.= N r-, __, uo N :J �o 0 N N� �o 0 N N-' jO N,C N N-' -' 0 " CHLORINE ROOM [[] = IDENTIFICATION LABEL LISTING CHEMICAL NAME N.C. = NORMALLY CLOSED EX. FINISHED FLOOR WATER SOFTENER (NEW AS OF SEPT. 2023) (TO BE REUSED) PROPOSED CHEMICAL FEED SCHEMATIC • � REVlSIONS � -; ' u a ·2 c=; -s � � ' � R, ,G 00 - BID SET C 2023 Midwestern Engi=rs. ]rn;. 802 West Ilro�dway Str\'el 1-'.0. Bc,x 295 loogwtee. Indiana 47S53 DATE NOV. 2023 DESIGN J.W.W. DRAWN M.M.C ,::'K.J.G Q.C. CHECK PROJECT NUMBER 2017043-01 M1 .07 32 OF 47 I FILE NUMBER 4 3 639 I Do Not Use Plan Previews for Take Off

RkJQdWJsaXNoZXIy NjAyODM2