Midwestern Engineers, Inc. Plan Preview
(4) #3/0 THWNI----� :>J," CONDUIT '--PROPOSED 277/480V-3¢, 4W ELECTRIC SERVICE TO LIFT STATION SITE BY NIPSCO -___...----4" SCH. 40 PVC CONDUIT w/ PULL ROPE, 36" LONG ...---- SWEEP ELBOWS AND 36" COVER BY CONTRACTOR. WIRE PROVIDED AND INSTALLED BY NIPSCO PROPOSED CT CABINET AND METER BASE BY CONTRACTOR, METERING BY NIPSCO )-200A-3P PROPOSED 200A-3P SERVICE ENTRANCE RATED, DELAYED TRANSITION AUTOMATIC TRANSFER SWITCH IN NEMA 4X S.S. ENCLOSURE G) 80A-3P ,___PROPOSED SOKW DIESEL STANDBY --+tlW'-'<-1- A -@ GENERATOR BY CONTRACTOR PD@ KEY NOTES (3) #10 THWN (1) #12 CU. GND. 1" CONDUIT (2) #12 THWN (1) #12 CU. GND. 1" CONDUIT (4) #3 THWN (1) #8 CU. GND. 2" CONDUIT (±) (2) #8 THWN (1) #10 CU. GND. 1" CONDUIT @ PUMPS HAVE VFD BUILT IN @ TOTAL PROTECTION SOLUTIONS SURGE PROTECTION DEVICE CAT# TK-ST120-3Y480-B-XX (OR EQUAL), LEADS TO BE AS SHORT AND STRAIGHT AS POSSIBLE #4 BARE CU. GND .. --i,f� IN ¥,"¢ CONDUIT EXOTHERMICALLY WELDED TO (3) l',"¢x10' CU. CLAD GND. RODS ON 1 O' TRIANGULAR SPACING PROPOSED PUMP CONTROL PANEL, 200A, 480V-3¢ IN NEMA 4X S.S. ENCLOSURE PROVIDED AND INSTALLED BY CONTRACTOR. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION "" 1 2 3 4 5 6 7,9 8 I I (3) #3/0 THWN (1) #4 CU. GND. 3" CONDUIT )-35A-3P )-35A-3P )-20A-2P )-20A-1P )-2DA-1P )-2DA-1P )-20A-2P )-20A-1 P CD NEMA 4X S.S. JUNCTION BOX: ----1 SUBMERSIBLE CABLING SUPPLIEDl ----1 BY PUMP MANUFACTURER THEN INSTALLED BY CONTRACTOR (TYP) @ 10HP PUMP #1 48DV-3¢ 14 FLA CD 10HP @ PUMP #2 480V-3¢ 14 FLA SKVA CONTROL TRANSFORMER 480V-1¢ PRl.- 120/240V-1¢ SEC. 0 CONTROL DUSK TO DAWN LIGHT ON SWITCH 720W GENERATOR BATTERY CHARGER t GENERATOR CONVENIENCE BLOCK RECEPTACLE HEATER WAYNE LIFT STATION PROPOSED ELECTRICAL ONE LINE DIAGRAM -- -· Not to sllALK EXISTING 120/240V-1¢, 3W OVERHEAD ELECTRIC SERVICE BY NIPSCO TO BE REMOVED BY NIPSCO. EXISTING .,, SECONDARY ACROSS HIGHWAY ANO CARRIER POLE TO REMAIN BEING THAT IT SERVES THE ADJACENT HOME. [7,y:;:c;;'I----EXISTING POLE MOUNTED METER #1489825 TO BE REMOVED BY NIPSCO. POLE, WEATHERHEAD, METER BASE, CONDUIT AND WIRE TO BE REMOVED BY CONTRACTOR. A--- EXISTING 100A-2P C.B. DISCONNECT F1 A P ANO GROUNDING ELECTRODE SYSTEM TO BE REMOVED BY CONTRACTOR / PUMP #1 24DV-1¢ 36 FLA PUMP #2 CONTROLS GFI RECEPT. SCADATA 240V-1¢ HEATER PANEL 36 FLA EXISTING WAYNE ST. LIFT STATION ELECTRICAL ONE LINE DIAGRAM NOT TO SCALE LEGEND ////, EQUIPMENT ANO MATERIAL TO BE DEMOLISHED BY CONTRACTOR \ \ EX. CAT ' H BASIN i'�__,,,! \ ' ! ! ' \ / / \ . EXISTING 120/240V-10 OVERHEAD ELECTRIC TO BE REMOVED BY NIPSCO I I '° i ! ' \ ! ! \ ' ! ! , \ ! ! \ \ EXISTING POLE MOUNTED METER #1489825 TO BE REMOVED BY NIPSCO. POLE, WGATHERHEAD, METER BASE, CONDUIT, WIRE AND REMAINING EQUIPMENT TO BE REM0Vf=Jj BY CONTRACTOR. i / \ ' 1 I , \ I / GENERATOR POWER DlG!TAL CONTROL ! ! \ ' i ! , \ 4" SCH. 40 PVC CONDUIT w/ PULL ROPE, 36" LONG SWEEP ELBOWS AND 36" COVER BY CONTRACTOR. WIRE PROVIDED AND INSTALLED BY NIPSCO. ! ! \ ' ! ! , \ ! ! \ ' : : ' \ i ! \ ' : i , \ ! ! \ ' I : • \ PROPOSED CARRIER POLE, RISER CONDUIT AND WIRE BY NIPSCO PROPOSED 50KW DIESEL STANDBY GENERATOR I ' ' i ) f t''- PR- O� Pe:, O_ S_ E _ D _ J_ U.L NC_ T _ IO- N-BO_ X_ I � I I '< ,., PROPOS6D ELECTRICAL EdUIPMENT RACK, SEE RISER , . .,. /rPOWER A CONTROL BATIERY CHARGER POWER -PUMP #1 POWER /''' -PUMP #2 POWER / -DIGITAL CONTROL . / '" -ANALOG CONTROL 9i,, . STONE \ "'',), . \ / y "" ! /� 'i' I '?,?1 ' ,. ·. ,,/ \\ / "" ! f/ \ \ 0 0\ \ \ \ \ \ . / \\ BLKT. I 'i' '< ,, J,/ 'i'q.\C) , ' ' ' I ' ' ' ' ' ' ' ' ' ' ' ' ' ' �. ' ' I ' ' ' ' ' ' ' I , ___ l /''' PROPOSED OVERHEAD A SECONDARY BY NIPSCO .. I I J I PROPOSED WAYNE STREET LIFT STATION 0 SCALE: 1" = 5'-Q" ELECTRICAL SITE PLAN • - REVISIONS / "" / "" ' BID SET 02024 Midwestern Engineers. Jnc. 802 \Ve.,t Ilruadw:,y Street P.O. Ilox 295 Loogootee. Tndiana47553 DATE MARCH 2024 DESIGN A.F.B. DRAWN C.N.M. Q.C. CHECK S.M.S. PROJECT NUMBER 2020073-00 29 29 OF 35 11 Fll.E NUMBER Lj L /093 Do Not Use Plan Previews for Take Off
Made with FlippingBook
RkJQdWJsaXNoZXIy NjAyODM2