0 • HVAC EQUIPMENT SCHEDULE L-1 PRICE INDUSTRIES - TRANSFER GRILLE MODEL# ATGH 14",6" DOUBLE FLANGE FRAME ASSEMBLY COLOR MATCH DOOR EF-1 GREENHECK - CEILING EXHAUST FAN MODEL# SP-B110 115 CFM @ 0.125" TOTAL EXTERNAL S.P. 30 WATTS, 120V-1¢ WC-6 ROUND HOODED WALL CAP HD-1 GLOBAL INDUSTRIAL - XLERATOR HAND DRYER 120V-1¢, 12.2A 1490W (HEAT ON), 425W (HEAT OFF) UH-1 QMARK - FAN FORCED WALL HEATER MODEL# LFK204F UH-2 240V-1¢, 8.3A, 2,000W, 6,824 BTUH, 100 CFM LFKSFCNW, 14 GAUGE SECURITY COVER, WHITE QMARK - BASEBOARD HEATER MODEL# QMKC2513W 120V-1¢, 6.5A, 750W, 2,559 BTUH TA2AW DOUBLE POLE THERMOSTAT PLAN NOTES (D TERMINATE 6" EXHAUST FAN AT EXTERIOR WALL WITH MANUFACTURER FURNISHED WALL CAP. @ INSTALL LOUVER CENTERED IN DOOR WITH BOTTOM 12" ABOVE GRADE. G) INSTALL WALL HEATER WITH BOTTOM 6" ABOVE FLOOR. BLOCK OUT WALL SO THAT HEATER IS ACCESSIBLE FROM CHASE. 2 GENERAL MECHANICAL NOTES MECHANICAL CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR REQUIREMENTS RELATING TO EQUIPMENT QUALITY, CONSTRUCTION AND FINISH OF MATERIALS. THESE DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION FOR PIPING, DUCTWORK, CONDUIT, ETC. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS AND FITTINGS MAY NOT BE SHOWN. CONTRACTOR SHALL INSTALL HIS WORK IN A MANNER THAT WILL CONFORM WITH THE STRUCTURE. CONTRACTOR SHALL AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND MAINTAIN MAXIMUM CLEARANCE WITHOUT FURTHER INSTRUCTION FROM THE ENGINEER OR ADDITIONAL COST TO THE OWNER. ALL DIMENSIONS SHOWN ON THESE PLANS ARE IN FEET AND/OR INCHES UNLESS NOTED OTHERWISE. ALL DUCTWORK, PIPING AND VALVES SHALL BE CONCEALED ABOVE CEILINGS AND WITHIN WALLS IN FINISHED AREAS UNLESS OTHERWISE NOTED. EQUIPMENT SIZES AND SERVICE SPACE REQUIREMENTS MAY VARY BETWEEN DIFFERENT MANUFACTURERS. CONSULT APPROVED MANUFACTURER DRAWINGS AS SUBMITTED, AND COORDINATE WITH THESE DRAWINGS. ALL EQUIPMENT SHALL BE OF, AND CONSIST OF AT LEAST THE MINIMUM SIZES SCHEDULED. ALL FIXTURES AND EQUIPMENT SHALL BE INSTALLED ALLOWING EASY ACCESS. AREAS ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF ANY OBSTRUCTIONS. EACH RESPECTIVE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE INSTALLATION OF HIS WORK WITH THE WORK OF OTHER CONTRACTORS PRIOR TO THE INSTALLATION. REFER TO ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL COORDINATION WITH THESE DRAWINGS. CONTRACTOR SHALL NOT LOCATE ANY DUCT OR PIPING DIRECTLY OVER ANY ELECTRICAL PANELS, SWITCH GEAR, TRANSFORMER, ETC. COORDINATE LOCATIONS OF DUCTS AND PIPING WITH THE ELECTRICAL CONTRACTOR TO AVOID THESE CONFLICTS. ALL HVAC SYSTEMS SHALL BE WIRED BY THE ELECTRICAL CONTRACTOR AND SHALL BE PLACED ON A DEDICATED CIRCUIT. SERVICE SPACE FOR EQUIPMENT SHALL NOT BE BLOCKED WITH PIPING, DUCTWORK, ETC. DUCTS PENETRATING ROOF, FLOOR SLABS AND/OR WALLS SHALL BE SEALED AS REQUIRED BY CODE. DUCTS PENETRATING FIRE RATED WALL AND/OR FLOOR SHALL HAVE OPENING AROUND DUCT SEALED WITH A MATERIAL HAVING THE SAME FIRE RATING AS THE WALL OR FLOOR. 2 - L.J---- - - -- UNISEX R.R.#1 UH 1 I I 3 II I / EF-1 6"¢ I I � I r 1 I 1 I / ,-----------,------ --- ,,. -- ,,. I HD-1 --- 3 I UH-1 UNISEX R.R.#2 II I � -�-A �- f - � P_ 1 , 9 _ . S _E_D_H_V_ A _C_P _ LA_N ,, [ � �-�U h--'""'---+1-1--+-h 6 "¢ I If---{ r-----n t-- ---t-i--J I EF-1 REVISIONS 10/25/23 BID SET 0 2023 Midwe.slem Engineers. Inc. 802 Wes! Broadway Strce1 P.O. Box 295 Loogootee, !ndi�na 47553 DATE OCTOBER 2023 DESIGN WAE DRAWN CNM a.c. CHECK CWR PROJECT NUMBER 2022024-05 40 40 OF 48 I FR£ NUMBER I 53549 Do Not Use Plan Previews for Take Off

RkJQdWJsaXNoZXIy NjAyODM2