·" " � 0 ! 0 �� Q --- Q �t '-.i ii '-Ill ... � - < .. - < � ,i Q :F � • l GENERAL ELECTRICAL NOTES NO MORE THAN SIX CURRENT CARRYING CONDUCTORS (INCLUDING NEUTRAL CONDUCTORS) IN ANY ONE CONDUIT CARRYING 20-AMP LIGHTING OR RECEPTACLE LOADS WITHOUT OERATING IN ACCORDANCE WITH NEC ARTICLE 310. ALL OTHER CIRCUITS SHALL BE IN A DEDICATED CONDUIT. PROVIDE GROUND CONDUCTOR IN ALL CONDUITS. SIZE PER NATIONAL ELECTRIC CODE. ALL WIRING SHALL COMPLY w/ THE LATEST EDITION OF THE INDL'.NA ELECTRIC CODE ANO COMPLY w/ COUNTY ANO/OR LOCAL JURISDICTION HAVING AUTHORITY IN THAT AREA. ELECTRICAL CONTRACTOR SHALL COORDINATE w/ ALL OTHER TRADES AND OWNER BEFORE WIRING IS TO BEGIN TO VERIFY ALL OTHER CONDITIONS SO THAT WIRING WILL NOT INTERFERE w/ THE OTHER TRADES. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED IN STRICT ACCORDANCE w/ THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ENTIRE ELECTRICAL SYSTEM SHALL BE INSTALLED IN A NEAT ANO WORKMANLIKE MANNER. ALL MATERIALS USED IN THE WORK SHALL BE APPROVED BY THE UNDERWRITER'S LABORATORIES, INC.. AND SHALL BEAR THEIR LABEL. THE CONTRACTOR SHALL, AT HIS/HER OWN EXPENSE, OBTAIN ALL PERMITS, INSPECTIONS, CERTIFlCATES, AND LICENSE REQUIRED BY LAW FOR THE EXECUTION OF WORK TO BE PERFORMED. THE ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED, SHALL FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT AS INDICATED ON THE DRAWINGS. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF FIRST CLASS CONSTRUCTION, AND SHALL BE THE PRODUCT OF AN ESTABLISHED AND REPUTABLE MANUFACTIURER, AND SHALL BE DESIGNED TO PERFORM THE SERVICE REQUIRED. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL HARDWARE, LAMPS, ACCESSORIES, ETC. AS REQUIRED FOR A COMPLETE AND WORKING SYSTEM. MULTI-WIRE (SHARED NEUTRAL CIRCUITS) SHALL NOT BE USED. PROVIDE A NEUTRAL CONDUCTOR FOR EACH LINE-TO-NEUTRAL CIRCUIT. ALL POWER AND CONTROL CIRCUIT WIRING USED SHALL BE IHHN" OR IHWN" COPPER UNLESS OTHERWISE SPECIFIED DR REQUIRED BY CODE. PER NEC 310.10, ALL WIRING SHALL BE SIZED TO COORDINATE w/ TEMPERATIURE RATINGS OF TERMINATIONS. LISTED WIRE SIZES ON PANELBOARD SCHEDULES ARE MINIMUM SIZES. SIZE WIRE TO MEET TEMPERATURE AND VOLTAGE DROP REQUIREMENTS. PROVIDE A PULL ROPE IN ALL SPARE CONDUITS. PROVIDE ID TAG AT EACH END OF PULL ROPE IDENTIFYNG LOCATION OF OPPOSITE END. ELECTRICAL SYMBOLS ARE NOT SHOWN TO SCALE. WHEN DEVICES ARE SHOWN ADJACENT, INSTALL IN ADJACENT BOXES. COMPLY w/ BOX FILL REQUIREMENTS OF NEC ARTICLE 314. ALL SAFETY SWITCHES SHALL BE "HEAVY DUTY" OWNER RESERVES FIRST RIGHTS TO ANY REMOVED EQUIPMENT AND MATERIALS. ALL UNWANTED EQUIPMENT AND MATERIALS SHALL BE DISCARDED BY CONTRACTOR PER LOCAL, STATE AND FEDERAL REGULATIONS AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR IS TO SEPARATE ALL POWER AND CONTROL CONDUITS. ALSO SEPARATE DIGITAL. ANALOG, ETHERNET, FlBER AND DATA. FlBER IS TO BE INSTALLED IN 2" CONDUIT w/ 90 DEGREE SWEEPING ELBOWS. ALL BURIED CONDUITS SHALL BE SCH. 80 PVC w/ MINIMUM 24" COVER w/ WARNING TAPE INSTALLED IN THE TRENCH 12" COVER. ALL EXPOSED CONDUITS OUTSIDE SHALL BE ALUMINUM FASTENED w/ STAINLESS HARDWARE. MINIMUM CONDUIT SIZE IS 1" EXCEPT FOR SWITCH LEGS WHICH CAN BE JI", TYPICALLY USE LONG SWEEP ELBOWS. CONDUITS SHOWN ON SITE PLAN OR DETAILS ARE FOR REFERENCE ONLY AND ARE NOT NECESSARILY INTENDED TO INDICATE EXACT QUANTITY OR LOCATION. CONTRACTOR IS TO QUANTIFY ALL REQUIRED PULL ANO JUNCTION BOXES PER NATIONAL ELECTRIC CODE. IN GROUND BOXES SHALL BE QUAZITE OR ENGINEER APPROVED EQUAL w/ COLOR SELECTED BY OWNER. EXTERIOR BOXES SHALL BE STAINLESS STEEL FASTENED w/ STAINLESS HARDWARE. ALL REQUIRED BYPASS PUMPING OR TEMPORARY POWER TO t.lAINTAIN PLANT OPERATIONS IS THE RESPONSIBILITY OF THE CONTRACTOR. COORDINATE ALL SCHEDULED OUTAGES w/ OWNER A MINIMUM Of 72 HOURS IN ADVANCE. ALL ABANDONED CONDUIT, WIRE ANO EQUIPMENT IS TO BE REMOVED; CAP CONDUITS ABOVE GRADE NOTING ORIGIN AND DESTINATION OF EACH END THEN NOTE ON AS-BUILT DRAWINGS. THE CONTRACTOR IS ALLOWED TO RE-USE EXISTING CONDUIT AND WIRE AS APPLICABLE AS LONG AS WIRE SPLICES ARE NOT REQUIRED. ANY WIRE THAT NEEDS EXTENDED, SHALL BE PULLED OUT ANO REPLACED w/ NEW PER NEC TO MATCH EXISTING. LOCATE ALL UNDERGROUND UTLITIES PRIOR TO EXCAVATION. CONTRACTOR SHALL FlELID VERIFY EXACT LOCATION OF CONDUIT, WIRE, JUNCTION BOXES, CONTROL PANELS AND EQUIPMENT w/ OWNER DURING CONSTIRUCTIDN PRIOR TO INSTALLATION. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO FIELID VERIFY EXISTING ELECTRICAL LOADS PRIOR TO BID. ALL EXISTING 480V-3• LOADS AND 12DV-1• LOADS REt.lAINING SHALL BE REROUTED AND RECONNECTED TO PROPOSED EQUIPMENT PER NEC. FlELID VERIFY EXACT LOCATION OF FlNAL CLARIFlER(S) 480V FEEDS, THEN RECONNECT AS SHOWN ON PROPOSED ONE LINE DIAGRAM. PANEL G CIRCUIT NO. 100AMPERES 12 □ /206 VOLTS .iWIRE ITEM FEED 1 DUSK TO DAWN LIGHT 3 SPARE 5 SPARE 7 SPARE 9 SPARE 11 SPARE 13 SPARE 15 SPARE 17 SPARE 19 SPARE 21 SPACE 23 SPACE 25 SPACE 27 SPACE 29 SPACE MCBMAIN CONNECTION 'PHASE eER Slllll:I'. KAJC WIRE AMPS POLE cu. SIZE BUS 12 20 1 A 12 20 1 B 12 20 1 C 12 20 1 A 12 20 1 B 12 20 1 C 12 20 1 A 8 20 2 B C 12 20 1 A B C A B C POLE 1 1 1 1 1 1 1 1 1 1 �EW El EC TRICAI el AIEQBM LOCATION SURFACE MOUNTING WIRE AMPS SIZE 20 12 RECEPTACLES 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE 20 12 SPARE SPACE SPACE SPACE SPACE SPACE CIRCUIT ITEM FEED NO. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 NOTE: CONTRACTOR TO PR0\11DE UPDATED TYPED AND LAMINATED PANEL SCHEDULE AT COMPLETION Of" PROJECT. PANEL 400AMPERES L 460VOLTS "WIRE CIRCUIT NO. ITEM FEED 1 PRIMARY SEWAGE PUMP CONTROL PANEL 3 SPACE 5 SPACE Ml OMAIN CONNECTION 'PHASE KAIC WIRE CU. SIZE AMPS POLE BUS 4 125 3 A B C 3 A B C 3 A B C POLE 3 3 3 �FW El EC TRICAl el 6IEQRM LOCATION SIJRFACE MOUNTING WIRE CIRCUIT AMPS SIZE ITEM FEED NO. 200 1/0 ROUGHING FlLTER PUMP 2 CONTROL PANEL SPACE 4 SPACE 6 NOTE: CONTRACTOR TO PROV1DE UPDATED TYPED AND LAMINATED PANEL SCHEDULE AT COMPLETION OF PROJECT. PANEL F CIRCUIT NO. 400 AMPERES 480VOLTS 'WIRE ITEM FEED 1 30KVA TRANSFOR�ER 3 FlNAL CLAAIFlER #1 5 NORTH PUMP CONTROL PANEL 7 SPACE 9 SPACE 11 SPACE 13 SPACE 15 SPACE Ml O MAIN CONNECTION 'PHASE KAIC WIRE CU. SIZE AMPS POLE BUS 8 50 3 A B C 12 20 3 A B C 8 50 3 A B C 3 A B C 3 A B C 3 A B C 3 A B C 3 A B C POLE 3 3 3 3 3 3 3 3 SIZED BY HINGED COVER - -- -.__,.. c _ o _ N _ TRA _ c T _ o _ R L INSTALL CLASS I DIV. I RATED CONDUIT SEAL-OFFS FROM CONTROL PANEL TO JUNCTION BOX, USE MYERS HUBS NOTE: LOCATE J.B. BEHIND OPENED LID, 60" AWAY FROM WETWELL VENT. FIELD LOCATE w/ OWNER PRIOR TO INSTALLATION. IUIICTIOII DOI fflBVl!ffll 111111,II S.S. WET WELL POWER DISTRIBUTION BLOCKS MOUNTED TO BACKPANEL INSIDE JUNCTION BOX INSTALL CABLE GRIPS TO SUPPORT CABLE OUT OF JUNCTION BOX (TYP.) VENTED ALUMINUM WIRE MESH CABLE GUARD w/ PAD LOCKABLE ACCESS . ... - .. ; . ,. .�� , ;;.r. ': ��: CORE DRILLED ENTRY TO WETWELL (TYP.) JUNCTION BOX DETAIL NOT TO SCALE EXISTING WOODEN STAND , ----f'c= TO BE REMOVED EXISTING JUNCTION BOX--TO BE REMOVED EXISTING WETWELL C4x2.33 ALUMINUM CHANNEL (2) ½"o STAINLESS STEEL STRONG-BOLT 2 BASE DETAIL NOT TO SCALE � - - . . ·• • > • • • • • • • • • • • • . • ' • .. •· . • . • • . .,· 4 • • EXiSTING • • • ' I WETWELL • • • -. • • • • ,• • • • •• :-ROPOSED LED OUSK TO DAWN LIGHT FIXTURE ON WP SWITCH 1¼" - " 4• ••• • • . . .. • • -� RIGID . . • , . ALUMINUM CONDUIT ALUMINUM UNI-STRUT C4x2.33 ALUMINUM CHANNEL PROPOSED FLOOD PUMP CONTROL PANEL IN NEMA 4X S.S. ENCLOSURE PROPOSED WEATHERPROOF GF1 RECEPTACLE (2) 480V-3o FEEDERS AND (1) DIGITAL CONTROL TO JUNCTION BOX, REUSE EXISTING 4BOV-3o HOMERUN PROPOSED JUNCTION BOX, SEE DETAIL THIS SHEET FLOOD PUMP CONTROL PANEL UPGRADES �FW El ECTRICAI ElAIEORM LOCATION SlJREACE MOUNTING WIRE I CIRCUIT AMPS SIZE ITEM FEED NO. 20 12 FINAL CLARIFlER #2 2 50 8 SOUTH PUMP CONTROL PANEL 4 SPARE 6 SPACE 8 SPACE 10 SPACE 12 SPACE 14 SPACE 16 NOT TO SCALE PROPOSED 4BOV-3o, 3W, 400A PANEL "L" PROPOSED 480V-3o, 3W, 400A PANEL •r STUB UP 2" SPARE FOR FUTURE SCAOA NETWORK =ED-14,16,18 ED-13,15,17 SEE SITE PLAN FOR CONTINUATION F\JTIURE SCAOA PANEL ALTERNATE BID ITEM PROPOSED 120/208V-3o, 3W, PANEL "G" F-1 PROPOSED 30 KVA TRANSFORMER G-1 L-1 PROPOSED LED OUSK TO DAWN LIGHT FlXTURE ON WP SWITCH NOTE: CONTRACTOR TO PROVIDE UPDATED lYPED AND LAMINATED PANEL SCHEDULE AT COMPLETION OF PROJECT. PROPOSED PRIMARY PUMP STATION CONTROL PANEL NOTE: PROVIDE UNISTRUT AS REQUIRED TO MOUNT EQUIPMENT, ANCHOR TO PLATFORM, DO NOT MOUNT TO HANDRAIL. NOTE: ALL EXPOSED CONDUITS ON PLATFORM SHALL BE ALUMINUM. PROPOSED ELECTRICAL PLATFORM SCALE: ½" = 1' -0" • RE\'1SIONS 1111 f,8 0,\ITlf I No. I- i PE111 i � - JE()f , . .. � \,� �� 4/12/24 BID SET i .,;,2024 Midwestern Engineers. Inc. 802 West BroadwaySlreel P.O. Bo., 295 o otee. lncliima 47553 O.TE APRIL 2024 DESIGN A.F.8. DRAWN C.N.M. Q.C. CHECK W.A.E. PROJECT NUMBER 2024019-00 5 5 or 11 FlLE NUMBER 44179 8 11 Do Not Use Plan Previews for Take Off
Made with FlippingBook
RkJQdWJsaXNoZXIy NjAyODM2