Type A B C D GENERAL ELECTRICAL NOTES NO MORE THAN SIX CURRENT CARRYING CONDUCTORS (INCLUDING NEUTRAL CONDUCTORS) IN ANY ONE CONDUIT CARRYING 20-AMP LIGHTING OR RECEPTACLE LOADS WITHOUT DERATING IN ACCORDANCE WITH NEC ARTICLE 310. ALL OTHER CIRCUITS SHALL BE IN A DEDICATED CONDUIT. PROVIDE GROUND CONDUCTOR IN ALL CONDUITS. SIZE PER NATIONAL ELECTRIC CODE. ALL WIRING SHALL COMPLY WITH THE LATEST EDITION OF THE INDIANA ELECTRIC CODE AND COMPLY WITH COUNTY AND/OR LOCAL JURISDICTION HAVING AUTHORITY IN THAT AREA. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR THE EXACT LOCATION AND ROUGH-IN REQUIREMENTS FOR ALL MECHANICAL EQUIPMENT AND PIPING BEFORE ROUGH-IN. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES AND OWNER BEFORE WIRING IS TO BEGIN TO VERIFY ALL OTHER CONDITIONS SO THAT WIRING WILL NOT INTERFERE WITH THE OTHER TRADES. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ENTIRE ELECTRICAL SYSTEM SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. ALL MATERIALS USED IN THE WORK SHALL BE APPROVED BY THE UNDERWRITER'S LABORATORIES, INC., AND SHALL BEAR THEIR LABEL. THE CONTRACTOR SHALL, AT HIS/HER OWN EXPENSE, OBTAIN ALL PERMITS, INSPECTIONS, CERTIFICATES, ANO LICENSE REQUIRED BY LAW FOR THE EXECUTION OF WORK TO BE PERFORMED. THE ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED, SHALL FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT AS INDICATED ON THE DRAWINGS. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF FIRST CLASS CONSTRUCTION, AND SHALL BE THE PRODUCT OF AN ESTABLISHED AND REPUTABLE MANUFACTURER, ANO SHALL BE DESIGNED TO PERFORM THE SERVICE REQUIRED. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL HARDWARE, LAMPS, ACCESSORIES, ETC. AS REQUIRED FOR A COMPLETE AND WORKING SYSTEM. MULTI-WIRE (SHARED NEUTRAL CIRCUITS) SHALL NOT BE USED. PROVIDE A NEUTRAL CONDUCTOR FOR EACH LINE-TO-NEUTRAL CIRCUIT. ALL POWER ANO CONTROL CIRCUIT WIRING USED SHALL BE "THHN" OR '1HWN" COPPER UNLESS OTHERWISE SPECIFIED OR REQUIRED BY CODE. PER NEC 310.10, ALL WIRING SHALL BE SIZED TO COORDINATE WITH TEMPERATURE RATINGS OF TERMINATIONS. LISTED WIRE SIZES ON PANELBOARO SCHEDULES ARE MINIMUM SIZES. SIZE WIRE TO MEET TEMPERATURE AND VOLTAGE DROP REQUIREMENTS. PROVIDE A PULL ROPE IN ALL SPARE CONDUITS. PROVIDE ID TAG AT EACH END OF PULL ROPE IDENTIFYING LOCATION OF OPPOSITE END. ELECTRICAL SYMBOLS ARE NOT SHOWN TO SCALE. WHEN DEVICES ARE SHOWN ADJACENT, INSTALL IN ADJACENT BOXES. COMPLY WITH BOX FILL REQUIREMENTS OF NEC ARTICLE 314. PROVIDE CONDUIT EXPANSION FITTINGS WHERE CROSSING BUILDING EXPANSION JOINTS. ALL SAFETY SWITCHES SHALL BE "HEAVY DUTY" OWNER RESERVES FIRST RIGHTS TO ANY REMOVED EQUIPMENT AND MATERIALS. ALL UNWANTED EQUIPMENT AND MATERIALS SHALL BE DISCARDED BY CONTRACTOR PER LOCAL, STATE AND FEDERAL REGULATIONS AT NO ADDITIONAL COST TO THE OWNER. LIGHT FIXTURE SCHEDULE Manufacturer / Model LITHONIA LIGHTING - 2GTL2 A12 120 LP840 (Cl-234TKW) 2X2 LED LAY-IN TROFFER LITHONIA LIGHTING - 4BEMW LED 30K 90CRI M6 / 4" RECESSED IC-RATED BAFFLE LITHONIA LIGHTING - TWS-LED-P1-50K-MVOLT-PE-DDB (EXTERIOR LED MINI WALL PACK) LITHONIA LIGHTING - LHQM-LED-R-HO EXIT/EMERG. LIGHT Mounting LAY-IN RECESSED SURFACE SURFACE D □ D □ CONTRACTOR TO ALLOW FOR 8 LIGHT FIXTURES TO BE INSTALLED IN EXISTING SLEEPING ROOMS 103/104 SIMILAR TO PROPOSED "A" FIXTURES. CONTRACTOR TO ALLOW FOR 5 RECEPTACLES EA. WITH USB PORTS TO BE INSTALLED IN EXISTING SLEEPING ROOMS 103/104. USE EXISTING CIRCUITS. � "DO NOT PENETRATE THROUGH FIRE WALL" PROVIDE JUNCTION BOXES AS NECESSARY TO RUN NEW WIRING IF NECESSARY. USE EMT OR SCH 80 CONDUIT FOR □□ EXPOSED WIRING. ASSUME 300 LF OF WIRING FOR LIGHTS & RECEPTACLES. D -· □I / / I I IJ □ 1 @ D □ □I Lamps 18W LED/ 2,223 LUMENS 10W LED/ 706 LUMENS 18W LED/ 2,124 LUMEN (2) -1.SW LED LAMPS w/ 90 MIN. NI-CAD BATTERY □ A 7 8 ...._ If' (' ,.J DISCONNECT ELEC. D SUB-PA �. � � • ••• - - � - · •• . 1 .• . .. . . a©·•.•.• : • : .. A-6 .•. .,·.• . .. . ' : ' : • . ., . .,. _. __ : : ', A-1 B \, )_ [_ -· ... ,Y . . . I I _x A 2 A-5 - \ "---+ �D @ ' I ' \ □ ll□l 11 □ 1 □ 11 □ 1 I 'i-------- - - I I J:<,, I> N 0 ' A � A .. - - - ' v � '-l.- - ---... 1 A-3 ◄' - - - A l I » f--" A .. i------ A-4�'C =� "al A • I I I ' - - - I/ L_ ----- � - - - II II = ELECTRICAL LIGHTING & POWER PLAN SCALE: 1/4" � 1'-0" REVISIONS BID SET C 2024 Midwestern Engineers. Inc. 802 West Bro,idway Stred P.O. Box 295 Loogootee, Indiana 47553 DATE JULY 2023 DESIGN T.M.K. DRAWN T.M.K. Q.C. CHECK C.W.R. PROJECT NUMBER 2021012-14 1 0 10 OF 11 ELECTRICAL PLAN I FILE NUMBER I 53786 Do Not Use Plan Previews for Take Off

RkJQdWJsaXNoZXIy NjAyODM2